● AC/DC main circuits with directly connected DC components, such as rectifiers
● Systems with switch-mode power supplies
Application
Characteristic
|
Auxiliary Power Supply |
Voltage |
AC85-265V |
||
|
Frequency |
40-60Hz |
|||
|
Power Consumption |
<8W |
|||
|
Voltage Range |
System Voltage |
AC/DC 0~480V |
||
|
Output |
Relay output |
Capacity |
Fault Warning |
AC 250V/3A |
|
Fault alarm |
AC 250V/3A |
|||
|
Environment |
Operating temperature |
-20~+60℃ |
||
|
Storage temperature |
-20~+70℃ |
|||
|
Humidity |
95%RH, without condensation |
|||
|
Altitude |
≤2500m |
|||
|
Insulation monitoring |
Measuring range |
1k-5MΩ |
||
|
Precision |
1-10k |
10k |
||
|
10k-5M |
10% |
|||
|
Early-warning range |
60k~4999Ω |
|||
|
Alarm range |
10k~Warning value |
|||
|
Response time |
<6s |
|||
|
Allowable system leakage capacitance |
<150uF |
|||
|
Communication |
Interface |
RS485 |
||
|
Protocol |
MODBUS-RTU |
|||
|
Internal parameters |
Measuring current |
<170uA |
||
|
EMC |
IEC61326-2-4 |
|||
|
Rated impulse voltage /pollution level |
8kV/Ⅲ |
|||
|
Internal DC resistance |
≥120kΩ |
|||