Monitor insulation resistance
Suitable for DC 0~1500V System
With Relay output
CE approval
General
With the development of industry, many electrical equipment and factory equipment are powered by DC systems, and the positive and negative poles of the DC system are not grounded. For ungrounded (IT) power distribution systems, insulation resistance should be monitored to ensure the safe operation of the power supply system.AIM-D100-ES DC Insulation Monitor can be used in 100~1500V DC systems to monitor the positive and negative pole-to-ground insulation resistance of ungrounded DC systems online. When the insulation resistance is lower than the set value, it will issue a pre-warning or alarm signal.The product is mainly designed for insulation monitoring of energy storage DC systems in the DC 100~1500V range. It can also be used in DC systems such as power plants, DC panels in substations, electric vehicle charging devices, UPS power supply systems, photovoltaic DC systems and other DC power grids.
Appearance
Details
Dimensions
Wiring
Technical Parameter |
Technical Specifications |
|
Auxiliary power |
DC 9~36V |
|
Maximum power consumption |
≤6W |
|
Voltage monitor |
Voltage range |
DC 100~1500V |
|
Accuracy |
0.5 |
Insulation monitoring |
Insulation resistance range |
1kΩ~10MΩ |
|
Warning and alarm range |
10kΩ~10MΩ |
|
Accuracy |
1~10kΩ: ±1k; 10k~500k: ≤3% |
|
System leakage capacitance |
≤5μF |
|
Insulation monitoring speed |
500ms/cycle; 1000ms/cycle |
Alarm method |
LED indicator |
|
Communication |
RS485 interface, Modbus-RTU protocol |
|
Installation |
Wall-mounted installation or DIN-rail installation (plastic stent included) |
|
Protection level |
IP30 |
|
Environment |
Operating temperature |
-40~+75℃ |
|
Storage temperature |
-40~+125℃ |
|
Relative humidity |
<95%, without condensation |
|
Altitude |
<2000m |