AGF-AE-D/200 is single phase energy meter follow the U.S electrical standard. It has a UL certificate and can also help users to measure different filed power energy. This energy meter supports single-phase three-wire system and is equipped with two split core current transformers with a maximum measuring current of 200A.
- LED Display
- Rated Input Voltage: L-N 120V, L-L 208/240V
- Rated Input Current: 200A AC CT Input
- Rated Frequency:45~60HZ
- UL list
- Grid Support: L1/L2/N/PE
- Single Phase Three Wire
- Communication: RS485(Modbus-RTU)
-
Used for distributed Solar PV
● Reflux Monitoring
● Connected with Load Line through CTs
● Directly connect with inverters1
-
Single-phase Three-wire Connection
● Rated Voltage of Line to N: 120V
● Rated Voltage of Line to Line: 208/240V
● Grids Supported: L1/L2/N/PE
2
-
Bidirectional Metering
● Active&Reactive Energy Metering
● Rated RMS Current: 200A
● Accuracy: ±0.5%/±1%3
Meter Electrical Service |
Units |
||
|
AGF-AE-D/100 |
AGF-AE-D/200 |
|
Rated Voltage-Line to N |
120 |
V |
|
Rated Voltage-Line to Line |
208/240 |
V |
|
Extended Voltage Range |
88%~110% |
|
|
AC Frequency |
60 |
Hz |
|
Grids Supported |
L1/L2/N/PE |
|
|
Power Consumption |
1.2 |
W |
|
Communication |
|||
Meter Communication Interfaces |
RS 485 |
|
|
Response Time |
≤1 |
S |
|
Meter Accuracy |
|||
Rated RMS current |
100 |
200 |
A |
1%-100% of CT Current |
±0.5 |
±1 |
% |
Current Transformers |
|||
Number of Supplied Current Transformers |
2 |
|
|
Dimensions |
I.D:15 O.D:35 |
70.5×54.5×39 (H×W×D) |
mm |
Standard Compliance |
|||
Safety |
UL1741 |
|
|
Installation Specifications |
|||
Dimensions(H×W×D) |
54.1×87.8×52 |
mm |
|
Weight |
0.2 |
kg |
|
Operating Temperature Range |
-30~55 |
℃ |
|
Relative Humidity (noncondensing) |
5 - 90 |
% |
|
Mounting Type |
DIN-Rail,35mm |
|