Acrel AMC16-DETT Multi-Circuits DC Energy Meter for Mobile Base & Tower Station
●DC rated voltage: 1 channel: -48VDC


●Rated Input Current:6 Channels:0~5VDC(with Hall sensor)


●Accuracy:1%In≤I≤10%In error±2.5%; I>10%In error±2%


●RS485(MODBUS-RTU)


●DIN Rail 35 mm

  • AMC16-DETT manual.pdf AMC16-DETT manual.pdf
  • Description
  • Technical Parameters

Brief Introduction

Base station DC energy meter AMC16-DETT is specially designed for base stations. The meter could measure 6 circuits DC energy, and provide the power supply for the matched hall sensors. Meanwhile, it can realize zero drift calibration by upper computer software.It also has the functions of telemetering,teleindication,teleadjusting, metering at real time, energy quality abnormal alarm, data storage and processing, data interaction. This meter can measure DC power consumption of three operators, providing detail datas for base station.

Characteristic

Communication

Single Channel RS485 communication protocol standard or customized

Display

LED indicator display

Rated U and I

Total 200A/5V

Function

Appearance

Dimension

Wiring

Application in base station

Recommended Products

ADL3000-E
AHKC-EKA
AMC16Z-FAK48


Technical parameter

Index


 input


DC rated voltage

1 channel: -48VDC

DC current

6 channels hall sensors output is 5V,current ratio can be set  according to the actual ratio


Commercial power
monitoring


1 channel transmitter input: 0-5VDC or 4-20mA


 
Overload capacity



Voltage:1.2times continued,2 times continued 1s;
Current: 1.2 times continued,10 times continued 1s.


Accuracy (superposition hall sensors)

1%In≤I≤10%In accuracy ±2.5%; I>10%In accuracy ±2%

 

Measurement resolution


Voltage output accuracy 0.01V;    current output accuracy 0.01A;
power output accuracy 0.01kw; energy output accuracy 0.01kWh.



 
 
 Functions



 
Basic function


Monitor device system time, total voltage, output total current, power, energy, each channel voltage, current, power, energy; LED indicator display;485 communication.


 
 
 
Metering function



Start current: under rated voltage, when the load current value of the meter doesn’t exceed 1% of the max. current, the meter starts.
Shunt running current: when there is no current in the current circuit of the meter, and 85%-125%of the rated voltage is applied on the voltage circuit, the calculator shall not have more than one digital change.



 
 
Alarm function


DC voltage output low alarm,DC voltage output high alarm,one power down alarm, module voltage loss alarm, metering branch error alarm, internal program error alarm, clock error alarm,memory failure alarm, AC input power failure alarm

 Timing function

support broadcast timing, could remote timing to the meter through RS485 communication.


 
Communication



Single channel RS485, baudrate 9600bps, can be set to 1200BPS, 2400bps, 4800bps.
Communication protocol: standard or custmized