Characteristics
- Remote monitoring
- Test button
- LED indicators:On, Insulation, Overload, Overtemp
- Auxiliary power supply: DC24V
- Mute button
- RS485(MODBUS-RTU)
Dimension
Wiring and Installation
LED indicator instructions
Indicator light |
Instructions |
On |
When the instrument operation is normal, the indicator flashes, with the flashing frequency of about one time per second. |
Insulation |
When the insulation resistance exceeds the alarm value, the indicator flashes to alarm. |
Overload |
When the load current exceeds the rated current of the transformer, the indicator flashes to alarm. |
Overtemp |
When transformer temperature exceeds alarm value, indicator flashes to alarm. |
Button function descriptions
Button |
Function descriptions |
Mute |
When there is alarm, press this button to eliminate the alarm sound. |
Test |
Used to start the self-test function of monitor. |
Common problems
Fault phenomenon |
Possible causes and troubleshooting |
Abnormal communication |
1) The address of AIM-M10 is not set to default 1, or BUAD is not set to default 9600, so it should be set to default value. 2) The communication line with AIM-M10 is not well connected. Check the communication line and confirm that the matching resistance is well connected. |
AUX POWER |
Voltage |
DC 24V |
|
Power consumption |
≤0.6W |
Insulation alarm range |
50-999kΩ |
|
Current alarm range |
14A、18A、22A、28A、35A、45A |
|
Temperature alarm range |
0~+200℃ |
|
Alarm mode |
Audible and visual alarm |
|
Alarm type |
Insulation fault, overload, overtemperature, device disconnection |
|
Communication mode |
RS485(MODBUS-RTU) |