AID10 Remote Alarm Indicators
  • description
  • Datasheet

Characteristics

  • Remote monitoring
  • Test button
  • LED indicators:On, Insulation, Overload, Overtemp
  • Auxiliary power supply: DC24V
  • Mute button
  • RS485(MODBUS-RTU)

Dimension

  • Front view
  • Side view

Wiring and Installation

  • 标题

LED indicator instructions

Indicator light

Instructions

On

When the instrument operation is normal, the indicator flashes, with the flashing frequency of about one time per second.

Insulation

When the insulation resistance exceeds the alarm value, the indicator flashes to alarm.

Overload

When the load current exceeds the rated current of the transformer, the indicator flashes to alarm.

Overtemp

When transformer temperature exceeds alarm value, indicator flashes to alarm.

Button function descriptions

Button

Function descriptions

Mute

When there is alarm, press this button to eliminate the alarm sound.

Test

Used to start the self-test function of monitor.


Common problems

For common problems, the causes can be determined and the faults can be eliminated according to the phenomenon of each instrument and the fault types:

Fault phenomenon

Possible causes and troubleshooting

Abnormal communication

1) The address of AIM-M10 is not set to default 1, or BUAD is not set to default 9600, so it should be set to default value.

2) The communication line with AIM-M10 is not well connected. Check the communication line and confirm that the matching resistance is well connected.

AUX POWER

Voltage

DC 24V

Power consumption

0.6W

Insulation alarm range

50-999kΩ

Current alarm range

14A18A22A28A35A45A

Temperature alarm range

0~+200

Alarm mode

Audible and visual alarm

Alarm type

Insulation fault, overload, overtemperature, device disconnection

Communication mode

RS485MODBUS-RTU